2 Hour Fire-Rated Cable - Single Pair
CIC/Free Air - Dual Rated
UL Listed
Part #s |
Length |
# of Pairs |
AWG |
Diameter |
Weight |
RP66010001 |
500' |
Single |
18 2-Conductor |
0.309" |
28 lbs. |
|
RP66010002 |
1,000' |
Single |
18 2-Conductor |
0.309" |
58 lbs. |
Applications:
- Manufacturing, commercial and industrial locations
- Colleges, banks, hotels, airports, and stadiums
- Health care facilities
- Tunnels and subways for emergency communications
- (EVAC) Emergency Voice-Alarm Communication Smoke and Fire Alarm Systems
- Fireman’s telephone and Area of Refuge Communication Systems
- Emergency lighting
Circuit-In-Conduit (CIC):
Hardware Certified for use in Systems FHIT .40A and FHITC .40A:
- 1/2-inch, 3/4-inch, 1-inch,1-1/4, 1-1/2-inch, and 2-inch EMT Conduit “E-Z Pull”– Allied Tube & Conduit Co. and Columbia-MBF
- 1/2-inch, 3/4-inch, 1-inch,1-1/4, 1-1/2-inch, and 2-inch Steel Compression Couplings – RACO or Thomas & Betts Corp
- Wiegmann NEMA 1 Enclosure/Pull Box
- Amtec wire mesh support grips for vertical installation beyond 30 feet
- Supports per the Comtran Cable installation instructions dated August 2016
Circuit Integrity Free Air (CI):
- For use as CI cable when installed per the NEC and local code. For vertical installation lengths beyond 30 feet, cables are to be supported using a Stainless Steel wire mesh
- Authorities Having Jurisdiction should be consulted before installation
Construction:
- Conductors: 18 AWG 2-Conductor Solid Copper specially engineered to minimize embrittlement due to fire exposure
- Tape: Flame Retardant Tape
- Insulation: Low Smoke, Zero Halogen Thermoset Fire-Roc™
- Core Assembly: Color Coded Insulated Conductors of Red and Black
- Jacket: Red, Low Smoke, Zero Halogen Polyolefin (Sequential Footage Marker Provided Every 2 Feet)