Both of RATH’s 2 Hour Fire-Rated cables meet NFPA-2016 code requirements
Will your local AHJ only accept an Underwriters Laboratory listing (UL)? Or will they accept cable that meets the European Standard (LU)?
UL (Underwriters Lab)
2 Hour Fire-Rated CableBenefits:
- Some AHJ’s require all wire to be UL
- Requires no special tools or training for installation
- Operating temperature 1,850° F
- Dual Rated CI/CIC
- New York City Approved
- California State Fire Marshal Approved
LU (London Underground)
2 Hour Fire-Rated CableBenefits:
- NFPA 72 approved by many jurisdictions
- Lower price than UL cable
- Operating temperature 1,742° F
- High speed data transfer approaching Cat 5E
- London Underground (LU) approved
- Available in 2 & 4 Pair
NFPA-2016
24.3.13.9.1 Area of Refuge emergency communications systems shall have a pathway survivability of Level 2 or Level 3.
(Level 1 is permitted where the building is less than 2-hour fire rated construction)
12.4.3 Pathway Survivability Level 2 Shall consist of one or more of the following:
(1) 2-hour fire rated circuit integrity (CI) or fire-resistive cable.
(2) 2-hour fire-rated cable system (electrical circuit protective systems)
(3) 2-hour fire-rated enclosure or protected area
(4) performance alternatives approved by the authority having jurisdiction
12.4.4 Pathway Survivability Level 3: shall consist of pathways in buildings that are fully protected by an automatic sprinkler system in accordance with NFPA13 and one or more of the following.
(1) 2-hour fire rated circuit integrity (CI) or fire-resistive cable.
(2) 2-hour fire-rated cable system (electrical circuit protective systems)
(3) 2-hour fire-rated enclosure or protected area
(4) performance alternatives approved by the authority having jurisdiction