2 Hour Fire-Rated Cable - 2 Pair
Part #s |
Length |
# of Pairs |
AWG |
Diameter |
Weight |
66102 |
500' |
2 |
18 4-Conductor |
0.465" |
61 lbs. |
|
66120 |
1,000' |
2 |
18 4-Conductor |
0.465" |
112 lbs. |
Applications:
- Emergency communications (i.e. telephones, speakers, etc.)
- Area of Refuge communication devices
- Addressable Class N fire alarm devices
- Critical data communication circuits
- For use in wet locations
Benefits:
- Only UL 2196 cable for 2 hour fire-rated circuits
- Unique solution for NFPA Level 2 or 3 requirements
- Supports all 10 Mbps critical data circuits
Construction:
- Conductors: 18 AWG 4-Conductor Solid Bare Copper
- Tape: Flame Retardant Tape
- Insulation: Low Smoke, Zero Halogen Thermoset Fire-Roc™
- Cable Assembly: 2 Pairs, White and Black Conductors
- Drain: 18 AWG Stranded Bare Copper
- Shield: Copper Shield
- Jacket: Red Non-Halogen Flame Retardant Polyolefin
Description:- Circuit integrity cables are the first to be UL 2196 while meeting Category 3 channel requirements. These shielded cables are available in 2 Pair 18 AWG construction and are capable of transmitting signals at a speed of 10 Mbps. In the event of a fire, these cables will ensure critical voice applications remain operational.